Article Overview

Proper CT configuration ensures accurate relay operation, prevents false tripping, and maintains system protection during faults and transients.

CT Selection and Accuracy

CTs must be selected based on the accuracy class and accuracy limit factor (ALF or Fa) to ensure reliable relay operation under fault conditions. For protection purposes, IEC 60044-1 recommends using CTs with a protection class (e.g., 5P10), where the number indicates the maximum permissible composite error at the rated accuracy limit current, and the letter “P” denotes protection use. The accuracy limit factor should typically exceed 20 to accommodate high fault currents without significant saturation . ANSI standards commonly use 5A or 1A secondary ratings, with the CT ratio chosen to limit the secondary current under maximum fault conditions to around 100A .

CT Sizing and Burden Considerations

CT sizing depends on the primary current, relay burden, and expected fault currents. The CT must remain in its linear region during internal faults to ensure correct tripping while avoiding false operation during external faults. The burden includes the relay input impedance and connecting leads; excessive burden can increase CT secondary voltage and risk saturation . Modern numerical relays have low input impedance, so the CT internal resistance and lead resistance are the primary contributors to burden .

Saturation and Transient Response

CT saturation occurs when the CT core cannot accurately reproduce the primary current, often due to high DC offset, high X/R ratio, or remanence. Saturation can distort the secondary current, causing delayed or false relay operation. Differential relays use percentage-slope characteristics to maintain security during CT saturation, ensuring that external faults do not cause false tripping . CTs should be selected to minimize saturation during expected system transients, including generator black starts or transformer energization .

Relay-Specific Configuration

  • Differential Protection (87G/87T): CTs must be matched in ratio and polarity across all phases to ensure accurate current summation. Any mismatch can produce false differential currents. CTs should be sized to handle maximum fault currents without exceeding the relay's input limits .
  • Overcurrent Protection: CTs must provide sufficient secondary current to operate the relay within its time-current characteristic. The start current setting is typically 70% of the CT nominal current to account for relay inaccuracies and CT errors .
  • Generator and Transformer Applications: CTs must accommodate high inrush currents and transient conditions. Using CT models validated against physical tests helps determine the required CT ratio, class, and burden for secure relay operation .

Practical Guidelines

  1. Match CT ratios and polarity across all elements in a differential zone.
  2. Select CTs with adequate accuracy class and limit factor to handle maximum fault currents.
  3. Consider CT burden including relay input and lead resistance to prevent saturation.
  4. Account for transient conditions such as DC offset, remanence, and inrush currents.
  5. Verify relay settings against CT performance to ensure correct operation under internal faults and security during external faults.
  6. Use separate CT cores for metering and protection if high accuracy is required for both functions . By following these requirements, protective relays can operate reliably, minimizing false trips and ensuring fast, selective fault clearing.

Applying CTs in protection schemes for transformers, generators

This technical article explains seven applications of CTs in protection schemes for generators, generator-transformers,

CT Polarity on a SIPROTEC Relay Quick Start Instructions

the CT star point towards the line or protected object. The currents used in the relay elements and oscillographic records follow the

How to Calculate Motor Protection Relay Settings Step

Calculate thermal overload, overcurrent, ground fault, and differential relay settings with

Transformer Differential and REF CT Configurations

In the "good old days" Transformer Differential protection and Winding Restricted Earth fault protection "had" to use

Current transformers for HV protection

The purpose of this study is to learn more about CT operation in association with protection relays and to lay down a few rules for

SEL-751 Feeder Protection Relay | Schweitzer Engineering Laboratories

The SEL-751 Feeder Protection Relay is ideal for directional overcurrent, fault location, arc-flash detection, and high-impedance fault

Protective Relaying

Typical Relay and Circuit Breaker Connections Protective relays using electrical quantities are connected to the power

Determining CT Requirements for Generator and Transformer Protective Relays

We consider CT models and compare the various models commonly available to laboratory test data to provide insight into the

Resistor Calculation for REF Protection

This document provides guidelines for setting restricted earth fault (REF) protection for transformer windings using a high impedance

Selecting CTs to Optimize Relay Performance

The derived equation provides the CT rating criterion for line protection in new installations and can identify the threshold of CT

CT Connection for Transformer Differential Protection

In this article, CT connection for transformer differential protection will be discussed. The analysis of different CT connections will be

Four Special Differential Protections And Their Respective CT

A differential protection monitors an area limited by CTs which measure incoming and outgoing currents. Now, let''s

NGR Ground Fault Relay Settings: 50/5 CT Configuration Guide

NGR ground fault relay coordination with 50/5 zero-sequence CTs. Covers pickup calculation, time dial settings, and

CT Connection for Transformer Differential Protection

Analysis of different CT connection for transformer differential protection and derivation of matrix equations used in modern numerical

Principles and protection applications of low-impedance bus

The relay is low impedance with a biased differential characteristic and includes means to detect CT saturation. The

Directional Overcurrent Protection

The selection of a CT depends not only on the CT specifications, but also on the network fault current magnitudes, desired protection

CT Requirements for GE MULTILIN Relays – Electrical Engineering

Distance protection. 17 Transformer Differential

CT Polarity On SIPROTEC Quick Start

This document provides instructions for setting CT polarity on SIPROTEC relays for 3 phase and restricted earth fault applications. It

Protection Relay Setting Interactive Calculator | FIRGELLI

With this Protection Relay Setting Calculator, you''ll be able to work out pickup current, time multiplier settings (TMS),

CT selection for Arcteq relays

On the other hand, a CT failure must be detected in order to block the relay and to avoid the relay''s false operation during external

CTs in Power System Protection

This article focuses on practical deployment: how CTs feed protective relays, how to select

CT Supervision Relay Working Principle

Protection CT Supervision Relay Working Principle CT supervision Relay Working Principle: In last study about high impedance

Delta-Wye Transformer Protection Relay Settings

Learn about protection relay settings for delta-wye power transformers, including CT connections and phase shift compensation.

CT Sizing for Generator and Transformer Protective Relays

Using CT models that were validated with a physical CT, along with simulations and hardware-in-the-loop testing, we determined the

ABB Relay CT Requirements Overview

This document outlines requirements for current transformers (CTs) used with ABB relays. It discusses CT classification, conditions

CT Selection for GE Multilin Relays

This document provides guidelines for selecting current transformers (CTs) to be used with GE Multilin protection relays. It discusses

Protection Basics

Review What is the function of power system protection? Name two protective devices For what purpose is IEEE device 52 used?

Protective Relay Basics Part 2

Part 1: Protective relay compared to low voltage circuit breaker. Review fundamental concepts, components, and terminology using

Restricted Earth Fault Protection of Transformer

It shall be noted that for a fault outside the Transformer i.e. for through fault Restricted Earth Fault Protection will not

Restricted Earth Fault Protection of Transformer | REF Protection

REF Protection Definition: REF protection is a scheme used in transformers to detect internal earth faults by

Related Resources

Need Precision Optical Test Instruments?

Request a free quote for OTDR, power meters, light sources, spectrum analyzers, return loss testers, VFL, or complete fiber test kits. EU‑owned manufacturer with local support in South Africa – reliable, accurate, and field‑proven equipment.